Products / Terminations, splices and accessories

Terminations, splices and accessories

Medium-voltage terminations, splices and separable connectors, compression lugs, cable cleats, glands and pulling accessories.

15 kV outdoor cold-shrink termination on a cable end, with a ground braid at the base, four silicone rain sheds, a top seal and a tinned two-hole compression lug.
  • Termination, base to lug
  • Cable jacket
  • Ground braid
  • Silicone rain sheds
  • Top seal
  • Compression lug
Voltage
600 V to 35 kV
Technology
Cold shrink; heat shrink; premolded
Connectors
200 A; 600 A
Conductor
Copper; aluminum
Wood utility pole carrying distribution lines and equipment

Applications

Terminations, splices and connectors are matched to the cable by voltage class, insulation diameter, shield type and conductor size, and supplied on the same purchase order.

  • Terminations at switchgear, transformers and riser poles
  • Splices in manholes, vaults and handholes
  • Separable connectors on pad-mounted equipment
  • Lugs, cleats and glands at equipment and in cable tray

Medium-voltage accessories

AccessoryDescriptionRatingStandard
TerminationsCold-shrink and heat-shrink, indoor and outdoor5 kV to 35 kVIEEE 48
SplicesCold-shrink, heat-shrink and premolded5 kV to 35 kVIEEE 404
Separable connectors200 A loadbreak elbows; 600 A deadbreak connectors15, 25, 35 kVIEEE 386
Shield grounding kitsTape shield and wire shield adapters5 kV to 35 kVIEEE 48

Connectors and installation

AccessoryDescriptionRatingStandard
Compression lugs and connectorsCopper and aluminum, one-hole and two-hole, long barrel600 V to 35 kVUL 486A-486B
Cable cleatsSingle and trefoil, stainless steel and polymerTo short-circuit ratingIEC 61914
Cable glands and MC connectorsFor armored and tray cable600 V to 35 kVUL 514B
Pulling eyes and gripsFactory-installed pulling eyes; pulling gripsTo cable sizeNot applicable
Installation materialsArc-proofing tape, pulling lubricant, end capsTo cable sizeNot applicable

Quotation

State the cable type, voltage class, insulation diameter and conductor size in the request.